Real & Reactive Power Transfer Formulas & Basics

The power triangle represents an essential building block to the understanding of power systems. Without indulging much in theories and formulas, it is crucial to understand how phase angles, voltage differences, and impedance help transfer real (MW) and reactive (MVAR) power.

                                            Real & Reactive Power Transfer Formulas & Basics                     

The power triangle represents an essential building block to the understanding of power systems. Without indulging much in theories and formulas, it is crucial to understand how phase angles, voltage differences, and impedance help transfer real (MW) and reactive (MVAR) power. 

To transmit MW from point A to B, the phase angle at point A must be leading. The amount of MW being transferred is a function of the phase angle difference. To transmit MVAR from point A to B, the voltage at point A must be higher than point B. The phase angle difference plays less of a significant role here. Therefore, it is important to have transformers and stations (i.e. 4 kV stations connected in a grid) under a tight voltage schedule in order to minimize circulating current/VARs.

Both real and reactive power is supplied by the generator down to the customer’s location. The ideal design is to have the transformers/supply feeders supply as much MW as they are rated for and to have other sources such as capacitor banks (see pictures below), line charging, etc. to supply the MVAR necessary to result in the transformer power factor being close to unity (please see formulas in figure 1).  

                                                   

                                            Distribution Capacitor

                                   

                                        Substation/Transmission Capacitor

To illustrate the above concepts, I have created station “Test” with three 138/13.8 kV step-down transformers that have identical impedances. The station load is 30 MW and the load power factor is 0.91 (by using the second equation in figure 1, the MVAR will be = 13.7 MVAR). The 138 kV and 13.6 kV are the base voltages for the system being studied; as seen in figure 3, the transmission voltage for this flow is around 142 kV and the distribution voltage is 14.2 kV, which is acceptable in this scenario. Transmission buses 5011, 5012 and 5013 each supply 10 MW and 5 MVAR to the substation (all transformers have the same impedance and all transmission feeders have the same source and impedance in this example). The delta between the 15 MVAR supplied to the high side of the transformers and the station reactive power load of 13.7 MVAR are losses through the step down transformers. As expected, the phase angles for buses 5011, 5012 and 5013 are leading the substation phase angle and that enables the MW power flow.

The real power transfer formula is shown in figure 2, in per unit and in MW, where E1 is voltage at point 1 (bus 5011) and E2 is voltage at point 2 (bus 5010). Z is the impedance between the two points (in this case, the transformer’s impedance), Z = R +jX, where R is the resistance and X is the reactance.  Ø is the phase angle difference between the two points.

Upon solving the formula, the MW flow from bus 5011 to bus 5010 is 10 MW.  This is the same as the MW in the load flow shown in figure 3.

 

The next step is to illustrate the reactive power transfer formula which is found in most power books, shown in figure 4, where we assumed that X >>R, and thus R = 0; the formula shows a MVAR value of -4.1 MVAR, which means that the reactive power is flowing from E2 to E1; this results doesn’t agree with the +5 MVAR shown in figure 3.

MVAR is a function of the voltage, to send power from E1 to E2, the voltage at E1 must be higher than E2; however, as seen from the per unit values in diagram 3, E2 is less than E1, even though E1 and E2 are on a different voltage base. The reason for the discrepancy is that the formula found in both books is usually utilized to calculate the reactive power flow between two buses; however, in this case we have a step-down transformer and the per-unit ratio (LTC position) makes a difference in the calculation. As seen from figure 3, the LTC position is 1.031, the reactive power transfer formula is correctly shown in figure 5 and the results concur with figure 3.

Figure 6 shows the revised Power transfer formula shown in figure 2 by considering the LTC position. 

Figure 7 shows the flows after a 10 MVAR capacitor bank was added and the third transformer was taken out of service. It is important to note that the following:

·The 10 MVAR capacitor bank is showing 10.8 MVAR; the reason for the increased VARs, is that capacitance is a function of the voltage squared; in the model, the base voltage was 13.6 kV and in the flow on figure 7, the station voltage was 14.104 kV, thus Capacitor MVAR  = (14.104/13.6)^2  x 10 MVAR = 10.8 MVAR.

·The remaining transformers supply less MVARs, due to the capacitor contribution

·Due to transformer 3 being out of service, the remaining transformers will supply the entire station load. The circuit now shows more impedance, because there are two parallel lines compared to the three lines

·The phase angle difference between bus 5011 and bus 5010 has increased from 1.92 (3 circuits in parallel) to 2.87˚

·The LTC position is showing 1.031LK (LK shows lock). This is the condition as soon as a contingency occurs, before the remaining transformers’ LTC start to move. This condition in PSS/E is called PTLF (Prior Transient Load Flow).

·Utilizing the formulas in figures 5 & 6: the flow on each in-service circuit is 15.03 MW & 2.3 MVAR, or 15.03 + j2.3, which is very close to the flow on figure 7.  

 

 

Discuss this Blog Entry 2

max (not verified)
on Jun 23, 2014

We have four 20mva transformers, connected in parallel on the secondary side. The transformers are
27-4.16/2.4kv and are fed with 27kv underground feeders about five miles long. All of the transformers are equipped with LTC. We were not able to put them (LTC) in auto position as the voltage drops on the 27kv lines are not identical. So the KVAR variation was affecting the secondary voltage and the LTC were hunting all the time. in addition, the total load should be as a minimum 25% of the transformer capacity or it was creating reverse power trip on 4.16kv side. For now the LTC are locked in middle position. Voltage on 4.16kv side varies +/- 2.5% as permitted by the IEEE.

Tang (not verified)
on Jun 29, 2014

Dear Sir,

You mentioned that MVAR can only flow from High Voltage (E1) to Lower Voltage (E2), right? But how can the -4.1 MVAR means the MVAR flowing from E2 to E1?

(the formula shows a MVAR value of -4.1 MVAR, which means that the reactive power is flowing from E2 to E1;) - found in the paragraph after Figure 2

Post new comment
or to use your TDWorld ID
What's The Grid Optimization Blog?

Got some wisdom to send out to over 50,000 power industry subscribers? Say it in the Grid Optimization Blog! Looking to write a blog or article? Want

Contributors

Matthew C. Cordaro, PhD

Dr. Matthew C. Cordaro, whose career spans many years as a senior executive in the utility industry, an educator, scientist and researcher in the fields of business, energy and environment, most...

Paul Mauldin

Paul earned his B.S. and an M.S. in electrical engineering from the University of California-Berkeley and is a registered professional engineer. He has worked in the energy industry for more than...
Blog Archive

Sponsored Introduction Continue on to (or wait seconds) ×