Switchgear application hybridization is an emerging field of deployment for distribution network switchgear such as automatic circuit reclosers (ACRs). The roles that these units fulfill on the network is diversifying rapidly, as the applicability of a single unit which incorporates circuit breaker, sensors and control has many applications.
A major recent development is the hybridization of a recloser to include sectionalizer functionality. To historic users of both of these technologies, it seems strange to reduce an ACR’s functionality to address a sectionalizer role. In a modern network, deploying a recloser or a sectionalizer is almost fiscally equal, making savings in inventory, training and organizational management of a single product a wise choice.
Historically, sectionalizers and reclosers worked in harmony, fulfilling two separate requirements. Reclosers were used as active protection devices, who used their sensors to detect fault situations and trip their circuit breaker to interrupt the fault current. As such, reclosers are considered “fault- breaking” devices. Multiple reclosers could be deployed along a single feeder to provide a segmentation of the line, so that a fault at the far end of the feeder would not result in a complete feeder outage. Provided that each downstream recloser was faster than the upstream unit, the unit closest to the fault would trip, and they would act in harmony.
This is philosophically the concept of protection grading. The total number of reclosers you could deploy, relies on how fast your first recloser has to be to beat the substation circuit breaker, and then the difference (grading margin) between each subsequent recloser along the line. When you ran out of margin, you couldn’t put in more traditional reclosers. But there is a device that cares less about grading, giving you more segmentation when you don’t have sufficient grading – these are sectionalizers.
The key difference between a sectionalizer and a recloser, is that the former does not have the capability to break fault current. But this is not necessary, because the objective is to operate in harmony with protection devices such as reclosers and other circuit breakers. Sectionalizers watch for fault current, then wait for upstream protection devices to operate, before opening in the time there is no current on the line – i.e. the dead time.
If a sectionalizer sees a fault, then a clearance, then it knows that there must be a downstream fault. Therefore, when it opens, it provides additional segmentation to the line.